HenSistemasHS-EMQA
Indoor air quality transmitters and controllers in two families. IAQW/IAQD respond to a wide range of airborne pollutants (VOCs): wood, paint and others produced by toluene, cigarette smoke, ammonia odor, CO, alcohol, natural gas and even body odor. IAQFW/IAQFD are dedicated to formaldehyde (CH2O) only.
IAQW/IAQFW models are for rooms; IAQD/IAQFD models are for duct mounting.
Price on request
No sign-up. You review the list and send it when you are ready.
Torn between two models?
Ask on WhatsAppSaves this product and the next ones you view in this browser, up to eight, for 30 days. You can disable it under “History” in the footer.
History is enabled in this browser. History
| Property | Value |
|---|---|
| Sensor | VOC: high-performance metal oxide semiconductor sensor; CH2O: high-performance electrochemical sensor |
| Power supply | 16~28VAC/16~35VDC |
| Measuring range | VOC: 0~2000ppm CO2 equivalent; CH2O: 0~1000ppb |
| Accuracy | CH2O: ±10%FS@25℃ |
| Output | 0~10VDC/4~20mA (default), RS485/Modbus |
| Display (IAQW/IAQFW) | Optional green/yellow/red LED air quality indication, or optional LCD display with unit and green/yellow/red backlight |
| Load resistance | ≤500Ω (current output), ≥2kΩ (voltage output) |
| Relay | 1×SPST, 3A/30VDC, 3A/250VAC |
| Working environment | 0~50°C, 0~95%RH (non-condensing) |
| Storage temperature | -20~60°C |
| Housing | ABS+PC (IAQW/IAQFW), fireproof ABS (IAQD/IAQFD) |
| Protection | IP30 (IAQW/IAQFW), IP65 (IAQD/IAQFD) |
| Weight | IAQW/IAQFW: ~190g; IAQD/IAQFD: ~395g |
| Approval | CE |